About 4:44 p.m., eastern standard time, on November 28, 2008, a three-car train operating along a fixed guideway on E Concourse at Miami International Airport near Miami, Florida, failed to stop at the passenger platform and struck a wall at the end of the guideway. Although a maintenance technician was monitoring train operations from the lead car of the train when the accident occurred, the train was operating in fully automatic mode without a human operator. The maintenance technician and five passengers on board the train were injured in the accident. One person on the passenger platform also required medical attention.
We determined that the probable cause of this accident was the installation by Johnson Controls, Inc., maintenance technicians of a jumper wire that prevented the overspeed/overshoot system from activating to stop the train when the crystal within the primary program stop module failed. Contributing to the accident were (1) the failure of Johnson Controls, Inc., to provide its maintenance technicians with specific procedures regarding the potential disabling of vital train control systems during passenger operations, (2) ineffective safety oversight by the Miami-Dade Aviation Department, (3) lack of adequate safety oversight of such systems by the state of Florida, and (4) lack of authority by the U.S. Department of Transportation to provide adequate safety oversight of such systems.
We made recommendations to the U.S. Department of Transportation, the 50 States and District of Columbia, Miami-Dade County, and Johnson Controls, Inc..