On March 9, 2000, about 10:20 p.m., central standard time, a 28-inch-diameter pipeline owned and operated by Explorer Pipeline Company (Explorer) ruptured and released 13,436 barrels (about 564,000 gallons) of gasoline. The pipeline was buried about 4 feet 6 inches under ranch land. The release site was near Greenville, Texas, about 45 miles northeast of Dallas.
Explorer’s Greenville pumping station on the 28-inch pipeline was about 10.3 miles south and upstream of the rupture site. This station automatically shut down its two running pumping units when the rupture occurred. Before the failure, the pipeline had been in steady-state operation, and its flow rate was approximately 20,000 barrels per hour. About 2 minutes after the rupture and the automatic shutdown of the Greenville pumping station, the pipeline controller (located in Tulsa, Oklahoma) started a different pumping unit at the Greenville pumping station in an effort to keep the entire pipeline balanced and operating. Meanwhile, the operator of the Greenville pumping station attempted to determine the cause of the automatic shutdown of his pumping units. The pumping unit that the controller had started also shut down automatically after about 2 minutes. The controller shut down the entire line. After a few minutes, thinking that the cause of the initial shutdown had been a control valve problem, the controller restarted the line at a reduced rate. About 13 minutes later (around 10:49 p.m.), the controller shut the entire line down for evaluation.
We determined that the probable cause of the pipeline failure was corrosion-fatigue cracking that initiated at the edge of the longitudinal seam weld at a likely pre-existing weld defect. Contributing to the failure was the loss of pipe coating integrity.