Safety Recommendation A-91-097
Details
Synopsis: ABOUT 0915 MOUNTAIN STANDARD TIME, ON SUNDAY, NOVEMBER 25, 1990, A FIRE ERUPTED AT A FUEL STORAGE AND DISPENSING FACILITY ABOUT 1.8 MILES FROM THE MAIN TERMINAL OF STAPLETON INTERNATIONAL AIRPORT AT DENVER, COLORADO. THE FACILITY, REFERRED TO AS A FUEL FARM, WAS OWNED BY UNITED AIRLINES AND CONTINENTAL AIRLINES. UNITED AIRLINES' PORTION OF THE FUEL FARM WAS OPERATED AND MAINTAINED BY AMR COMBS. FROM THE TIME FIREFIGHTING EFFORTS WERE INITIATED IMMEDIATELY AFTER THE FIRE ERUPTED UNTIL THE FIRE WAS EXTINGUISHED, A TOTAL OF 634 FIREFIGHTERS, 47 FIRE UNITS, AND 4 CONTRACT PERSONNEL EXPENDED 56 MILLION GALLONS OF WATER AND 28,000 GALLONS OF WATER AND 28,000 GALLONS OF FOAM CONCENTRATE. THE FIRE BURNED FOR ABOUT 48 HOURS. OF THE 5,185,000 GALLONS OF FUEL STORED IN TANKS AT THE FARM BEFORE THE FIRE, ABOUT 3 MILLION GALLONS WERE EITHER CONSUMED BY THE FIRE OR LOST AS A RESULT OF LEAKAGE FROM THE TANKS. TOTAL DAMAGE WAS ESTIMATED BY UNITED AIRLINES TO HAVE BEEN BETWEEN $15 AND $20 MILLION. NO INJURIES OR FATALITIES OCCURRED AS A RESULT OF THE FIRE.
Recommendation: THE NTSB RECOMMENDS THAT THE FEDERAL AVIATION ADMINISTRATION: REQUIRE OPERATORS OF FUEL FARM FACILITIES ON THE PROPERTY OF CERTIFICATED AIRPORT TO INSTALL FAIL-SAFE CONTROL VALVES AND INTERNAL FIRE VALVES WITH FUSIBLE LINKS ON ALL ABOVE-GROUND FUEL STORAGE TANKS.
Original recommendation transmittal letter: PDF
Overall Status: Closed - Acceptable Alternate Action
Mode: Aviation
Location: Denver, CO, United States
Is Reiterated: No
Is Hazmat: No
Is NPRM: No
Accident #: DCA91FZ001
Accident Reports: Fuel Farm at Stapleton International Airport
Report #: AAR-91-07
Accident Date: 11/25/1990
Issue Date: 10/9/1991
Date Closed: 1/26/1993
Addressee(s) and Addressee Status: FAA (Closed - Acceptable Alternate Action)
Keyword(s):

Safety Recommendation History
From: NTSB
To: FAA
Date: 1/26/1993
Response: BECAUSE THE FAA HAS CONTACTED ALL PART 139 CERTIFICATE HOLDERS REGARDING THE SUBJECT OF THESE RECOMMENDATIONS, THE BOARD IS PLACING RECOMMENDATIONS A-91-97 THROUGH -99 IN A "CLOSED--ACCEPTABLE ALTERNATE ACTION" STATUS. ALTHOUGH WE HAVE CLOSED THESE RECOMMENDATIONS, WE WOULD APPRECIATE BEING INFORMED OF ANY RESPONSE YOU RECEIVE FROM YOUR MAY 6, 1992, LETTER TO ALL PART 139 CERTIFICATE HOLDERS.

From: FAA
To: NTSB
Date: 11/18/1992
Response: IN SUMMARY, FAA TOOK THE POSITION THAT FUEL STORAGE FACILITIES ARE DESIGNED BY SKILLED EXPERTS ACCORDING TO APPLICABLE STATE AND LOCAL CODES THAT INCORPORATE DESIGN STANDARDS FROM THE AMERICAN PETROLEUM INSTITUTE (API) AND THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), THAT THE EXISTING PROCESS HAS RESULTED IN A SAFE AND EFFICIENT OPERATION AND SERVED THE PUBLIC EFFECTIVELY IN THE PAST, FAA DOES NOT HAVE SUFFICIENT EXPERTISE IN THIS DISCIPLINE TO PROVIDE EFFECTIVE OVERSIGHT, AND THAT THE EXPERTS MUST BE GIVEN LATITUDE TO CHANGE SAFETY DEVICES BASED UPON THE MOST CURRENT PRACTICES. AS AN ALTERNATE ACTION, THE FAA DISTRIBUTED THESE RECOMMENDATIONS, ON MAY 6, 1992, TO ALL 14 CFR PART 139 CERTIFICATE HOLDERS AND REQUESTED THE HOLDER TO INSPECT THE ON-AIRPORT FUEL FACILITY WITH APPROPRIATE ENGINEERS AND FIRE INSPECTION STAFF TO DETERMINE WHAT ADDITIONAL SAFETY DEVICES SHOULD BE INSTALLED AND TO MAKE NECESSARY CHANGES. BEYOND THIS, THE FAA PLANS NO FURTHER ACTION ON THESE RECOMMENDATIONS.

From: NTSB
To: FAA
Date: 2/4/1992
Response: Safety Recommendation A-91-97 urged the FAA to require the installation of fail-safe valves and fire valves on above-ground storage tanks. Safety Recommendation A-91-98 asked the FAA to require placing an emergency shutoff switch and recording equipment outside of fuel spill containment areas. In Safety Recommendation A-91-99, the Board urged the FAA to examine the feasibility of mandating the use of temperature and vibration monitoring and shutdown equipment on all fuel pumping systems on property of certificated airports. In response to these three recommendations, the FAA stated that fuel storage facility design and safety issues are best left up to the experts that design fuel storage facilities and to the State and local codes that reflect industry standards. Further, the FAA stated that this "historical policy" has resulted in the safe and efficient design and operation of fuel farm facilities. The Safety Board concluded from its investigation that if these safety features had been in place at the time of the equipment failure, this major fire and loss of fuel and equipment would have been very minor. Further, the design experts to whom you have referred have totally redesigned the new fuel farm at Denver's new airport subsequent to the fire because they did not foresee the consequences of this type of equipment failure. The safety devices suggested in these recommendations are state-of-the-art and their incorporation in all above ground fuel storage facilities on certificated airport property would enhance the safety of these facilities. However, the Safety Board agrees that decisions to incorporate such devices may be made more appropriately by qualified personnel after an analysis of each facility. Therefore, your response that the safety devices identified in the recommendations should be brought to the attention of the airport operators, and that each operator should be required to inspect on-airport fuel facilities with the appropriate engineer and fire inspector to determine what additional safety devices need to be installed, is an acceptable alternative to our requested action. Based on this action, Safety Recommendations A-91-97, -98, and - 99 are being held in an "Open--Acceptable Alternate Response" status. The Board requests that you keep us informed of the progress on this alternate action and that the response of the certificate holder to the required safety review be transmitted to the Safety Board.

From: FAA
To: NTSB
Date: 12/23/1991
Response: IN SUMMARY, FAA TOOK THE POSITION THAT FUEL STORAGE FACILITIES ARE DESIGNED BY SKILLED EXPERTS ACCORDING TO APPLICABLE STATE AND LOCAL CODES THAT INCORPORATE DESIGN STANDARDS FROM THE AMERICAN PETROLEUM INSTITUTE (API) AND THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), THAT THE EXISTING PROCESS HAS RESULTED IN A SAFE AND EFFICIENT OPERATION AND SERVED THE PUBLIC EFFECTIVELY IN THE PAST, FAA DOES NOT HAVE SUFFICIENT EXPERTISE IN THIS DISCIPLINE TO PROVIDE EFFECTIVE OVERSIGHT, AND THAT THE EXPERTS MUST BE GIVEN LATITUDE TO CHANGE SAFETY DEVICES BASED UPON THE MOST CURRENT PRACTICES. THE FAA DOES PLAN TO DISTRIBUTE THIS RECOMMENDATION TO THE CERTIFICATE HOLDERS AND REQUIRE THE HOLDER TO INSPECT THE ON-AIRPORT FUEL FACILITY WITH APPROPRIATE EXPERTS TO DETERMINE WHAT ADDITIONAL SAFETY DEVICES SHOULD BE INSTALLED. BEYOND THIS, THE FAA PLANS NO FURTHER ACTION ON THIS RECOMMENDATION.